What is diesel bug, and why does it stop a standby generator?

Fuel5 min readRevised Written by Generator Servicing Company

A canopied standby generator beside wall-mounted power equipment

In brief

Diesel bug is a growth of bacteria and fungi that lives where water meets diesel in a tank. It forms sludge that can block filters when the set draws fuel hard. Standby tanks are prone to it because the fuel sits for a long time. Draining water, testing the fuel and polishing it are the usual answers.

On this page
  1. What diesel bug actually is
  2. Why there is water in the tank at all
  3. Why standby generators are hit hardest
  4. Signs to look out for
  5. What can be done about it
  6. A worked example
  7. The tank matters as well
  8. Why this is part of maintenance

If you have heard the phrase before, it was probably from a service engineer holding up a jar of dark, cloudy fuel. Diesel bug sounds like a nickname, and it is. But the problem behind it is real, and standby generators are among the places it does most harm.

This post covers what diesel bug is, why a standby tank gives it such an easy life, what the signs are and what can be done about it.

What diesel bug actually is

Diesel bug is a loose name for microbes, mainly bacteria and fungi, that grow in stored fuel. They don’t live in the diesel itself. They live in water, and feed at the boundary where water and fuel meet.

As they grow, they form a slimy mat and a dark sludge. Some of it settles at the base of the tank. Some of it hangs in the fuel and gets drawn towards the outlet. In other words, the fuel stops being just fuel.

Why there is water in the tank at all

Most people assume a sealed tank stays dry. In practice, water finds its way in over time: condensation inside a tank that warms and cools, rain getting past a worn cap or vent, or water already present in a delivery.

There is also the fuel itself. Road diesel in the UK is made to BS EN 590, which allows up to 7% FAME, the biodiesel part of the blend. FAME takes up water more readily than mineral diesel does. That doesn’t make modern diesel bad fuel, but it does mean a tank that sits for a long time has more water to work with.

Why standby generators are hit hardest

A delivery van’s tank is emptied and refilled every few days. A standby generator’s tank may sit full for years, topped up now and then after a test run. That long, quiet storage is exactly what the microbes need.

And the way a standby set uses its fuel makes the problem worse. For most of its life it draws very little. Then the mains fails, it starts and runs hard, and suddenly it pulls fuel through the system much faster than it ever does in a short test. If there is sludge near the outlet, that is the moment it reaches the filters.

What happens Why it matters for a standby set
Water collects at the base of the tank Gives microbes somewhere to grow
Sludge forms where fuel meets water Can be drawn towards the outlet
Filters block under heavy draw The set can starve of fuel and stop
Tank linings and parts corrode Shortens the life of the fuel system

Signs to look out for

You may not see anything until something goes wrong. But there are a few signs worth acting on.

  • Fuel filters blocking early, especially if the engineer finds black or slimy deposits in them.
  • Dark, hazy or cloudy fuel in a sample, rather than clear fuel.
  • Water at the tank base when the engineer checks.
  • A set that starts, runs briefly and stops, particularly during a longer run.

If any of these come up, it’s very important to deal with the fuel before relying on the set again. A generator that has just been serviced can still fail if its fuel is contaminated.

What can be done about it

There isn’t one fix, and the right answer depends on how bad the fuel is. In a lot of cases the engineer will work through these steps in order.

  1. Take a sample and test it, so you know what you are dealing with.
  2. Drain off free water from the base of the tank.
  3. Polish the fuel: circulate it through filters and water separators until it runs clean.
  4. Treat it if the engineer recommends a treatment.
  5. Retest to show the fuel is back in good order.

Our page on fuel polishing for generator tanks explains that service in more detail.

A worked example

Say you look after an office with a standby set that has been tested monthly for ten minutes and has never had a long run. At the annual service, the engineer replaces the fuel filters and finds them darker than expected. A sample from the tank base comes out cloudy with a layer of water.

The sensible next steps would be to drain the water, polish the fuel, and book a longer run under load once the fuel is clean, so you can see the set carry real work. After that, a fuel sample at every major service gives you early warning if the problem comes back.

The tank matters as well

While someone is looking at the fuel, it’s worth looking at the tank too. In England, oil stored above ground at a business in a container over 200 litres usually needs secondary containment, such as a bund holding 110% of the tank. There are exemptions, for example some tanks inside a building that would hold a leak (Control of Pollution (Oil Storage) (England) Regulations 2001). Scotland has its own rules, set by SEPA.

A bund full of rainwater, a damaged cap or a vent that lets in water all make diesel bug more likely. Fixing them is usually cheaper than cleaning the fuel again next year.

Why this is part of maintenance

The Electricity at Work Regulations 1989 put a duty on whoever controls an electrical system to maintain it so it doesn’t cause danger, so far as is reasonably practicable. For a building that depends on its standby set, that includes making sure the set will actually run. Fuel is part of that.

If you’d like one engineer to look at the set, the tank and the fuel together, our generator servicing company page is the place to start.

A fuel sample costs little next to a set that stops halfway through a power cut. Ask for one at your next visit using the form below.

Sources for this post

Ask for a quote for your generator

We look for one service engineer who works in your area and tell you who they are before any of your details go to them. You pay nothing for this.

  1. You tell us where the set is and what it needs.
  2. We name an engineer who covers your site.
  3. You say yes or no before your details are passed on.
  4. They quote in writing, directly to you.

Step 1 of 3

Where is the generator?
Get a quote